mypros+
Error code reference

LG Heat Pump Error Code E307

PWM DISCHARGE TEMP sensor error OPEN/SHORT. Detected when outdoor temperature is over -10°C. Error level

Avg. service call
$285
National average. Trip fee plus diagnostic plus labor. Before parts.
MyPros+ 3-day pass
$9.95
Same diagnostic steps, on your phone. Start now.
You keep in your pocket
~$275
Even before you buy the part.
Skip the service call. Fix it yourself.
Full procedure unlocks instantly.
Get Started

What the E307 error code actually means

Your LG heat pump is showing an error because the sensor that monitors how hot the compressor is running has either lost its connection or stopped working correctly. The system cannot safely operate without knowing the compressor temperature, so it shuts down to protect itself. A technician will need to check the wiring and the sensor to get the unit running again.

Diagnostic procedure

The full E307 procedure

Step 1 is visible so you can confirm you are on the right page. The remaining steps, the ones that tell you whether to actually replace a part, unlock with any pass.

MyPros+ · DiagnosticsStep 1 preview
1
First diagnostic step
Check if digital compressor discharge temperature sensor connector is separated from PCB; measure resistance.
More steps, wiring diagram references, and verified part numbers
Includes expected resistance and voltage values, connector pinouts, and supersession notes for replacement parts.
Unlock E307 procedure $9.95

Or subscribe: $29/month for unlimited access to all codes plus Max AI diagnostics.

Most common causes of E307

Ranked by how often they cause this code
  1. 1Disconnected sensor connector at PCB
  2. 2Failed discharge temperature sensor (thermistor)
  3. 3Damaged or broken sensor wiring harness
  4. 4Corroded or damaged connector pins
  5. 5Faulty outdoor PCB

Most DIYers save hundreds by diagnosing before ordering parts.

Get Started

$29/month · Cancel anytime · Or $9.95 3-day pass

Questions people ask about E307

What does E307 mean on a LG heat_pump?
E307 indicates a fault in the PWM discharge temperature sensor circuit connected to the digital compressor. The control board has detected a signal voltage above 4.95V (open circuit, corresponding to below -30°C) or below 0.5V (short circuit, corresponding to above 151°C). This error is only active when outdoor temperatures are above -10°C. The system stops normal operation to protect the compressor until the fault is resolved.
Is it safe to keep running my heat pump with an E307 error?
No. The E307 error means the system cannot monitor the compressor discharge temperature, which is a key safeguard against compressor overheating. Operating the unit without a functioning discharge sensor risks serious and potentially irreversible compressor damage. The unit should remain off until the sensor fault is diagnosed and repaired.
How much does it cost to repair an E307 error on an LG heat pump?
Repair costs vary depending on what is causing the fault. If only the sensor connector needs to be reseated, the cost is primarily a service call fee, typically in the range of $75 to $150. Replacing the discharge temperature sensor itself generally runs between $50 and $150 for the part plus labor. If the outdoor PCB requires replacement, costs can range from $300 to $700 or more depending on the model and labor rates in your area.
Can I fix E307 myself, or do I need a technician?
A knowledgeable DIYer can start by checking whether the discharge temperature sensor connector is fully seated on the outdoor PCB, since a loose connector is the most common cause. However, accurately measuring the sensor resistance and diagnosing wiring or PCB faults requires a multimeter and familiarity with reading circuit values. If the connector appears secure and the error persists, a qualified HVAC technician should complete the diagnosis.
Will resetting the heat pump clear the E307 error?
A power reset may temporarily clear the error display, but if the underlying fault in the sensor, wiring, or connector is still present, E307 will return once the unit attempts normal operation. The error condition is based on a live voltage reading from the sensor circuit, so a reset alone does not resolve the root cause. The sensor and wiring must be inspected and repaired for the error to clear permanently.

78,000+ service manuals · 160,000+ error codes · 55+ brands

Get Started

$29/month · Cancel anytime · Or $9.95 3-day pass