U-Line Ice Maker Error Code L Temp Hi 6H+
Left zone temperature is +10° over set point for over 6 hours.
Left zone temperature is +10° over set point for over 6 hours.
First step from the service manual
Verify door is closed and sealing. Contact customer care if persistent.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for L Temp Hi 6H+.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What L Temp Hi 6H+ means on a U-Line ice maker
The L Temp Hi 6H+ error code on a U-Line ice maker indicates that the temperature in the left zone has been running at least 10 degrees Fahrenheit above the user-configured set point continuously for more than six hours. This is a sustained thermal fault, meaning the unit has had an extended period where it cannot maintain the desired cooling target. The left zone temperature sensor is actively monitoring this condition and triggers the alert once both thresholds, the 10-degree deviation and the 6-hour duration, are met simultaneously.
This type of prolonged temperature elevation typically points to a problem with either heat infiltration from the environment or a loss of cooling capacity within the refrigeration circuit. Common culprits include a door that is not closing fully or whose gasket has degraded, allowing warm ambient air to continuously enter the compartment. Refrigeration system issues such as low refrigerant charge, a failing evaporator fan, or a condenser that is clogged with debris can also reduce the unit's ability to recover temperature after a load event.
Because the fault requires six hours of sustained elevated temperature to trigger, it is less likely to be caused by a brief door opening or short-term ambient spike. The persistence of the condition is the key diagnostic indicator. Verifying proper door seal and closure is the recommended first step, as this is the most accessible and frequently overlooked cause. If the error persists after confirming the door is sealing correctly, the refrigeration system and its components require further inspection by a qualified technician.
Source: manufacturer service documentation.
Common causes of L Temp Hi 6H+
- 01
Door not fully closed or poor gasket seal
Wiring / connectionA door left ajar or a worn, cracked, or dirty door gasket allows warm ambient air to continuously enter the left zone, overwhelming the cooling system. Inspect the gasket around its entire perimeter for tears, stiffness, or gaps, and confirm the door latches fully when pushed shut.
- 02
Dirty or blocked condenser
Wiring / connectionDust and debris accumulation on the condenser coils reduces the unit's ability to reject heat, causing temperatures to rise above set point over time. Inspect the condenser and clean it if buildup is present.
- 03
Evaporator fan failure
Part replacementIf the evaporator fan motor has stopped running or is running intermittently, cold air will not circulate properly through the left zone, causing a sustained temperature rise. Listen for fan operation and check that airflow can be felt inside the compartment.
- 04
Low refrigerant charge or refrigeration system fault
Part replacementA refrigerant leak or a failing compressor will reduce cooling capacity, making it impossible for the unit to maintain set point temperatures over an extended period. This requires a certified technician with proper equipment to diagnose and repair.
- 05
Left zone temperature sensor fault
Part replacementA faulty or out-of-calibration temperature sensor in the left zone may be reporting inaccurate readings, triggering the error even when actual temperatures are within range. This diagnosis typically requires reading sensor output values and comparing them to actual compartment temperature.
Frequently asked questions about L Temp Hi 6H+
What does L Temp Hi 6H+ mean on a U-Line ice_maker?
How do I fix the L Temp Hi 6H+ error on my U-Line ice maker?
Will resetting the unit clear the L Temp Hi 6H+ error?
Is the L Temp Hi 6H+ error a safety concern?
How much does it cost to repair the L Temp Hi 6H+ error on a U-Line ice maker?
78,000+ service manuals · 160,000+ error codes · 55+ brands
Get Started$29/month · Cancel anytime · Or $9.95 3-day pass