U-Line Ice Maker Error Code R Temp Lo 6H+
Right zone temperature is -10° under set point for over 6 hours.
Right zone temperature is -10° under set point for over 6 hours.
First step from the service manual
Check compressor, evaporator fan and related relays and DC outputs.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for R Temp Lo 6H+.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What R Temp Lo 6H+ means on a U-Line ice maker
The R Temp Lo 6H+ error code indicates that the right zone temperature has measured at least 10 degrees Fahrenheit below the configured set point for a continuous period exceeding 6 hours. This is a sustained low-temperature fault, meaning the unit is not simply experiencing a brief cold spike but rather a prolonged condition where the refrigeration system is either overcooling or failing to maintain the correct thermal environment. The right zone typically encompasses the ice-making compartment or a dedicated storage section, depending on the specific U-Line model configuration.
The primary suspects for this fault are the compressor, the evaporator fan, and the associated control relays and DC output signals that govern their operation. If the evaporator fan is running continuously without proper cycling, or if a relay is stuck in a position that keeps the compressor or fan energized beyond its normal duty cycle, the zone can be driven well below the set point. A failed temperature sensor could also report falsely low readings, triggering this code even if actual temperatures are within range.
Diagnosis should begin by verifying compressor operation and duty cycle, then inspecting the evaporator fan for continuous or erratic running. Check all associated relays for proper switching behavior and confirm that DC output signals from the control board are within expected parameters. Sensor resistance values should also be measured and compared against the expected temperature-to-resistance curve to rule out a faulty thermistor as the root cause before replacing mechanical components.
Source: manufacturer service documentation.
Common causes of R Temp Lo 6H+
- 01
Stuck or faulty relay
Part replacementA relay controlling the compressor or evaporator fan may be stuck in the closed position, keeping the component running continuously and driving zone temperatures far below the set point. Inspect each relay for proper switching and listen for audible clicking during normal cycle transitions.
- 02
Evaporator fan running continuously
Wiring / connectionIf the evaporator fan does not cycle off at the correct times, it will move cold air through the right zone without interruption, causing extended overcooling. Check the fan motor and its DC output signal to confirm it is receiving proper on/off commands from the control board.
- 03
Control board DC output fault
Part replacementThe control board may be sending incorrect DC output signals to the compressor or fan, preventing normal cycling. Measure the DC outputs at the board terminals and compare against expected values to determine if the board is commanding components incorrectly.
- 04
Faulty temperature sensor or thermistor
Part replacementA defective thermistor in the right zone may report temperatures that are significantly lower than actual conditions, causing the unit to log this fault without a true overcooling event. Measure sensor resistance and cross-reference it against the expected resistance curve for the ambient temperature.
- 05
Compressor not cycling off properly
Wiring / connectionA compressor that fails to shut down at the end of its cooling cycle will continuously drive down zone temperature. Verify that the compressor is receiving proper stop signals and that run times align with expected duty cycles for the set point.
Frequently asked questions about R Temp Lo 6H+
What does R Temp Lo 6H+ mean on a U-Line ice_maker?
Can I fix the R Temp Lo 6H+ error myself on my U-Line ice maker?
Is it safe to keep using my U-Line ice maker while the R Temp Lo 6H+ code is active?
How much will it cost to repair the R Temp Lo 6H+ error on a U-Line ice maker?
Will resetting my U-Line ice maker clear the R Temp Lo 6H+ error code?
78,000+ service manuals · 160,000+ error codes · 55+ brands
Get Started$29/month · Cancel anytime · Or $9.95 3-day pass