mypros+
Error code reference

Goodman Air Conditioner Error Code C5

Outdoor Coil temperature too high for outdoor ambient temperature.

Outdoor Coil temperature too high for outdoor ambient temperature.

First step from the service manual

Check for Blocked Outdoor Air or Clean Coil.

The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.

MyPros+ Max

Get the full diagnostic procedure for C5.

  • Step-by-step tests with expected resistance, voltage, and continuity values
  • Wiring diagram references and connector pinouts from the OEM service manual
  • Verified part numbers when replacement is required
Get the full procedure

$29/month · Cancel anytime · Or $9.95 3-day pass

What C5 means on a Goodman air conditioner

The C5 error code on a Goodman air conditioner indicates that the outdoor coil temperature is registering too high relative to the measured outdoor ambient temperature. This condition is monitored by the control board using input from the outdoor coil temperature sensor. Under normal operation, the coil temperature during cooling should remain within an expected range above or below the ambient reading. When the coil temperature exceeds the threshold the control logic expects for the current ambient conditions, the C5 fault is triggered and the unit may lock out to protect the refrigerant circuit and compressor.

The most frequent cause of this fault is restricted airflow across the outdoor condenser coil. A coil clogged with dirt, grass clippings, cottonwood seeds, or other debris reduces the system's ability to reject heat, causing coil temperatures to rise abnormally. Similarly, a failing condenser fan motor or bent/damaged fan blade will reduce airflow volume, producing the same effect. The first diagnostic step is a visual inspection of the coil surface for blockage and a check of the condenser fan for proper operation and correct rotation direction.

Less commonly, C5 can be caused by refrigerant overcharge, a faulty outdoor coil temperature sensor reporting an incorrect reading, or a defective control board misinterpreting a valid sensor signal. If airflow is confirmed to be adequate and the coil is clean, technicians should check the sensor resistance against specifications and verify the refrigerant charge using manifold gauges. Overcharge conditions elevate head pressure and coil temperature and require refrigerant recovery before recharging to the correct weight or pressure specification.

Source: manufacturer service documentation.

Common causes of C5

  1. 01

    Dirty or Blocked Outdoor Coil

    Wiring / connection

    Accumulated dirt, debris, cottonwood seeds, or grass clippings on the condenser coil fins restrict airflow and trap heat, causing coil temperature to spike. Inspect the coil surface on all sides and clean with coil cleaner or a low-pressure rinse if buildup is present.

  2. 02

    Condenser Fan Motor Failure or Reduced Speed

    Part replacement

    A failing fan motor that runs slowly or intermittently will not move enough air across the coil to dissipate heat properly. Check that the fan spins freely, runs at the correct speed, and rotates in the proper direction when the unit is operating.

  3. 03

    Blocked Airflow Around Outdoor Unit

    Wiring / connection

    Overgrown shrubs, fencing, stored items, or debris placed too close to the unit can recirculate hot discharge air back through the coil. Ensure at least the minimum required clearance on all sides and the top of the unit.

  4. 04

    Refrigerant Overcharge

    Wiring / connection

    Too much refrigerant in the system raises head pressure and elevates condenser coil temperatures beyond the expected range for the ambient conditions. Diagnosis requires manifold gauge readings and should be performed by a licensed technician.

  5. 05

    Faulty Outdoor Coil Temperature Sensor

    Part replacement

    A defective or out-of-calibration coil temperature sensor can report falsely elevated temperatures, triggering C5 even when the coil is operating normally. Check the sensor resistance value against the specification for the measured temperature and replace the sensor if it is out of range.

See the test procedure for each cause

Frequently asked questions about C5

What does C5 mean on a Goodman air_conditioner?
The C5 code means the outdoor coil temperature is too high for the current outdoor ambient temperature. The control board monitors both values and triggers this fault when the coil reading exceeds the expected threshold. It is most commonly caused by a dirty condenser coil or restricted airflow around the outdoor unit. The system may lock out to protect the compressor until the condition is corrected.
How do I fix a C5 error on my Goodman air conditioner?
Start by turning off the unit and inspecting the outdoor condenser coil for dirt, debris, or blockage on all sides. Clean the coil if needed and make sure there is adequate clearance around the unit with no obstructions. Also check that the condenser fan is spinning freely and in the correct direction. If the coil is clean and airflow is unobstructed, a technician should check the refrigerant charge and the coil temperature sensor.
Will resetting my Goodman air conditioner clear the C5 code?
A power reset may temporarily clear the C5 fault and allow the unit to restart, but if the underlying condition is not resolved, the code will return. Repeatedly resetting the unit without fixing the cause risks overheating and damaging the compressor. Address the airflow or coil issue first before attempting a reset.
Is it safe to run my Goodman AC when it shows a C5 error?
It is not recommended to continue running the unit while the C5 code is active. Elevated coil and refrigerant temperatures place significant stress on the compressor, and continued operation can lead to compressor failure or other component damage. Turn the system off and diagnose the cause before restarting.
How much does it cost to repair a Goodman C5 error code?
The cost depends on the root cause. Cleaning a dirty coil is typically a low-cost service call ranging from around $75 to $200. Replacing a condenser fan motor can range from $150 to $450 including parts and labor. If refrigerant correction or a control board replacement is needed, costs can range from $200 to $600 or more depending on the specific repair required.

78,000+ service manuals · 160,000+ error codes · 55+ brands

Get Started

$29/month · Cancel anytime · Or $9.95 3-day pass