LG Hvac Error Code 10
LS902HPV/LS122HPV/LA09xHV/LA12xHV
LS902HPV/LS122HPV/LA09xHV/LA12xHV: PCB sees ODU discharge pipe thermistor open/shorted. All other Inverters/PTAC: ODU fan motor not rotating or not proving rotation. 10/13 SEER: IDU fan failure.
First step from the service manual
Discharge thermistor: must be 244,000Ω at 20°C/68°F & 24,400Ω at 90°C/194°F. Fan motor: verify 310V DC on motor wires; 0V DC=failed PCB, 310V DC=likely failed motor. Unplug and spin: 0V DC=motor caused board failure, 14-30V DC=good motor.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for 10.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What 10 means on a LG hvac
Error code 10 on LG HVAC systems covers two distinct fault conditions depending on the model. On LS902HPV, LS122HPV, LA09xHV, and LA12xHV units, the outdoor unit PCB has detected that the discharge pipe thermistor is either open-circuit or short-circuit. On all other inverter models and PTAC units, error code 10 indicates that the outdoor unit fan motor is not rotating or is failing to prove rotation to the control board. On 10/13 SEER systems, this code points to an indoor unit fan failure instead.
For the discharge thermistor fault, the sensor monitors refrigerant temperature at the compressor discharge line and is critical for protecting the compressor from overheating. A properly functioning thermistor should read approximately 244,000 ohms at 20 degrees Celsius (68 degrees Fahrenheit) and drop to approximately 24,400 ohms at 90 degrees Celsius (194 degrees Fahrenheit). Readings outside these values confirm a failed or disconnected thermistor. Wiring harness damage, connector corrosion, or thermistor degradation are common causes.
For the fan motor fault, the diagnostic process centers on DC bus voltage at the motor leads. The outdoor fan motor should receive 310 volts DC when commanded to run. A reading of 0 volts DC points to a failed control PCB that is not supplying drive voltage. If 310 volts DC is present but the motor does not run, the motor itself is the likely failure. To protect the board during diagnosis, the motor should be unplugged and spun manually: 0 volts DC measured after unplugging suggests the motor was back-feeding and causing board damage, while a reading of 14 to 30 volts DC confirms the motor is electrically sound.
Source: manufacturer service documentation.
Common causes of 10
- 01
Outdoor fan motor failure
Part replacementThe outdoor unit fan motor has seized or lost its windings and is not rotating despite receiving 310V DC drive voltage from the PCB. This is confirmed when voltage is present at motor leads but the motor does not spin.
- 02
Discharge pipe thermistor open or shorted
Part replacementOn applicable inverter models, the thermistor has failed or its wiring has been damaged, causing a resistance reading outside the expected range of 244,000 ohms at 20°C or 24,400 ohms at 90°C. Inspect the sensor and connector for corrosion or physical damage.
- 03
Failed outdoor unit control PCB
Part replacementIf 0V DC is measured at the fan motor leads when the motor should be running, the PCB is not supplying drive voltage and has likely failed. This must be ruled out before replacing the motor.
- 04
Fan motor back-feeding and damaging the PCB
Part replacementA failing fan motor can feed voltage back into the control board, causing board damage. If the motor reads 0V DC after being unplugged and manually spun, the motor is the root cause of board damage and both components may need replacement.
- 05
Wiring harness or connector issue
Wiring / connectionLoose, corroded, or broken connections at the thermistor plug or fan motor connector can cause the PCB to register an open or missing signal. Inspect all connectors in the circuit before replacing components.
Frequently asked questions about 10
What does 10 mean on a LG hvac?
Can I fix error code 10 on my LG HVAC myself?
Is it safe to keep running my LG unit when error code 10 is displayed?
How much does it cost to repair LG HVAC error code 10?
Will resetting my LG HVAC clear error code 10?
78,000+ service manuals · 160,000+ error codes · 55+ brands
Get Started$29/month · Cancel anytime · Or $9.95 3-day pass