LG HVAC Error Code 10

LS902HPV/LS122HPV/LA09xHV/LA12xHV: PCB sees ODU discharge pipe thermistor open/shorted. All other Inverters/PTAC: ODU fan motor not rotating or not proving rotation. 10/13 SEER: IDU fan failure.

SourceLG Ductless HVAC & PTAC - Tech Sheet: Error Codes & Wiring

Diagnostic procedure

The full 10 procedure

Step 1 is visible so you can confirm you are on the right page. The remaining steps, the ones that tell you whether to actually replace a part, unlock with any pass.

MyPros+ · DiagnosticsStep 1 preview
1
First diagnostic step
Discharge thermistor: must be 244,000Ω at 20°C/68°F & 24,400Ω at 90°C/194°F. Fan motor: verify 310V DC on motor wires; 0V DC=failed PCB, 310V DC=likely failed motor. Unplug and spin: 0V DC=motor caused board failure, 14-30V DC=good motor.

SourceLG Ductless HVAC & PTAC - Tech Sheet: Error Codes & Wiring