Error code reference
Carrier Air Conditioner Error Code 5
Open Circuit
Open Circuit — Compressor power circuit is open.
First step from the service manual
Check if condensing unit power disconnect is open, compressor circuit breaker or fuses are open, compressor contactor has failed open, high pressure switch is open and requires manual reset, broken supply wires or connector not making contact, or unusually long compressor protector reset time.