LG Hvac Error Code 27
Inverter compressor amperage over 100A for a split second.
Inverter compressor amperage over 100A for a split second.
First step from the service manual
Verify proper 208/240V AC feeding unit, ensure not in high-head situation, verify 3 compressor windings all equal at 1-4Ω, verify ∞Ω to ground, check amperage, check reactor connections and verify reactor resistance is less than 1Ω.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for 27.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What 27 means on a LG hvac
Error code 27 on an LG inverter-driven HVAC system indicates that the inverter compressor drew an amperage spike exceeding 100 amps, even if only momentarily. The inverter drive board monitors compressor current in real time, and when current surges to this extreme level the system shuts down to protect the compressor windings, the inverter module, and the power circuit components. A spike of this magnitude points to either an electrical supply problem, a mechanical load problem inside the compressor, or a fault in the drive circuitry itself.
The most important first checks involve the power supply and the compressor's electrical integrity. The unit requires a stable 208/240V AC input, and a low or unbalanced supply voltage can force the inverter to draw excessive current trying to maintain compressor speed. The compressor windings themselves must be verified: all three windings should measure between 1 and 4 ohms relative to each other and should show infinite resistance to ground. Any winding that reads outside these values points to a failed compressor. A high-head pressure situation, caused by a dirty outdoor coil, blocked airflow, or refrigerant overcharge, dramatically increases the mechanical load on the compressor and can trigger this current spike.
The reactor, which is an inductor wired in series with the compressor circuit to smooth inverter output current, is another critical component to inspect. Its resistance should measure below 1 ohm. A loose reactor connection or an open reactor can disrupt current flow and cause erratic amperage behavior that triggers error 27. All reactor wiring terminals should be checked for tightness and signs of arcing or heat damage before replacing any major components.
Source: manufacturer service documentation.
Common causes of 27
- 01
High head pressure condition
Wiring / connectionA blocked or dirty outdoor coil, restricted airflow around the unit, or refrigerant overcharge increases compressor mechanical load drastically, causing current to spike above 100A. Check outdoor coil cleanliness and ensure the unit has adequate clearance on all sides.
- 02
Low or unbalanced supply voltage
Wiring / connectionInsufficient or unstable 208/240V AC input forces the inverter to compensate by drawing higher current, which can produce extreme momentary spikes. Measure voltage at the unit's terminal block under load to confirm the supply is within spec.
- 03
Failed or degraded compressor windings
Part replacementIf any of the three compressor windings read outside the 1 to 4 ohm range or show any continuity to ground instead of infinite resistance, the compressor has failed internally and is drawing excessive current. This requires compressor replacement.
- 04
Loose or failed reactor connections
Part replacementThe reactor is wired in series with the compressor to smooth inverter current output, and its resistance must be below 1 ohm. Loose terminals or an open reactor disrupts current regulation and can cause the spike that triggers error 27. Inspect all reactor wiring connections for looseness, arcing, or heat damage.
- 05
Faulty inverter drive board
Part replacementIf the power supply, compressor windings, reactor, and head pressure all check out correctly, the inverter board itself may be misreading or generating abnormal current output. This requires board-level diagnosis or replacement.
Frequently asked questions about 27
What does 27 mean on a LG hvac?
Can I fix error code 27 on my LG HVAC myself?
Is it safe to keep running my LG unit when error code 27 appears?
Will resetting the unit clear error code 27?
How much does it cost to repair error code 27 on an LG HVAC?