LG Hvac Error Code 29
Inverter compressor high amperage.
Inverter compressor high amperage.
First step from the service manual
Verify proper 208/240V AC feeding unit, ensure not in high-head pressure condition, verify 3 compressor windings all equal at 1-4Ω, verify ∞Ω to ground, check amperage.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for 29.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What 29 means on a LG hvac
Error code 29 on an LG inverter-driven HVAC system indicates the inverter compressor is drawing excessive amperage during operation. The inverter drive board monitors current draw from the variable-speed compressor continuously, and when amperage exceeds the acceptable threshold, this fault is triggered to protect both the compressor and the drive electronics. This is a protective shutdown, not a nuisance trip, and the underlying cause must be identified before the system is restarted.
High amperage conditions in an inverter compressor typically stem from one of three categories: electrical supply problems, mechanical load problems, or compressor winding faults. On the electrical side, low or unbalanced supply voltage at 208/240V AC forces the compressor to draw more current to maintain its output, so verifying proper voltage at the unit under load is a critical first step. High-head pressure conditions, caused by a dirty condenser, refrigerant overcharge, or non-condensables in the system, increase the mechanical load on the compressor and directly raise current draw.
On the compressor itself, winding resistance should be checked across all three terminals. Each winding should measure equally in the 1 to 4 ohm range, and resistance from any winding terminal to ground should read infinite (open circuit). A winding-to-ground fault or unequal winding resistance indicates internal compressor failure. If windings test within spec and voltage is confirmed correct, the inverter drive board itself may be misreading current or failing to regulate output frequency properly, making the drive board a secondary suspect after the compressor and system pressures are ruled out.
Source: manufacturer service documentation.
Common causes of 29
- 01
High refrigerant head pressure
Wiring / connectionA dirty condenser coil, blocked airflow around the outdoor unit, refrigerant overcharge, or non-condensables in the system increase the compressor's mechanical load and cause current to spike. Inspect the condenser coil for debris and check system pressures with manifold gauges.
- 02
Low or incorrect supply voltage
Wiring / connectionThe unit requires a stable 208/240V AC supply. Low voltage forces the compressor to draw higher amperage to compensate, triggering this fault. Measure voltage at the unit's disconnect under operating load to confirm it is within spec.
- 03
Compressor winding fault
Part replacementIf any of the three compressor windings reads outside the 1 to 4 ohm range, reads unequal compared to the others, or shows measurable resistance to ground instead of infinite resistance, the compressor has an internal failure and requires replacement.
- 04
Failed or faulty inverter drive board
Part replacementIf supply voltage, system pressures, and compressor windings all test within specification, the inverter board may be delivering incorrect frequency or voltage to the compressor or inaccurately sensing current. The drive board is the secondary suspect after other causes are ruled out.
- 05
Compressor seized or mechanically binding
Part replacementA compressor that is beginning to seize internally will draw extremely high locked-rotor or near-locked-rotor current even if windings test correctly on a static resistance check. Abnormally high amperage confirmed with a clamp meter during a start attempt points to this condition.
Frequently asked questions about 29
What does 29 mean on a LG hvac?
Can I fix error code 29 on my LG HVAC myself?
Is it safe to keep running my LG HVAC when error code 29 appears?
How much does it cost to repair error code 29 on an LG HVAC?
Will resetting the unit clear error code 29 on a LG HVAC?