LG Hvac Error Code 41
PCB sees inverter compressor discharge pipe thermistor as open or shorted.
PCB sees inverter compressor discharge pipe thermistor as open or shorted.
First step from the service manual
Thermistor must be 244,000Ω at 20°C/68°F, 24,400Ω at 90°C/194°F. Ohm thermistor in water; with perfect thermistor & plug connection, change PCB.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for 41.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What 41 means on a LG hvac
Error code 41 on an LG HVAC system indicates that the PCB (printed circuit board) has detected an abnormal signal from the inverter compressor discharge pipe thermistor. This thermistor is a negative temperature coefficient (NTC) sensor mounted on the discharge line of the inverter compressor. It monitors the temperature of refrigerant gas leaving the compressor, which is a critical data point for protecting the compressor from overheating and for regulating system operation. When the PCB reads a resistance value that falls outside the expected range, it interprets the thermistor as either open (infinite or very high resistance) or shorted (near-zero resistance) and triggers error code 41.
The correct resistance values for this thermistor are approximately 244,000 ohms at 20 degrees C (68 degrees F) and 24,400 ohms at 90 degrees C (194 degrees F). Any reading significantly outside these benchmarks confirms a faulty sensor. Testing should be performed by submerging the thermistor tip in water at a known temperature and measuring resistance with a multimeter. This method isolates the sensor itself from any wiring or connector issues.
If the thermistor resistance tests within specification at both temperature points, the fault likely lies in the wiring harness or connector between the sensor and the PCB. Inspect the connector pins for corrosion, bent terminals, or intermittent contact. If both the thermistor and all connections check out as good, the PCB itself is the suspect component and will need replacement.
Source: manufacturer service documentation.
Common causes of 41
- 01
Failed discharge pipe thermistor
Part replacementThe thermistor itself has failed internally, producing a resistance reading that is either open or shorted. Confirm by measuring resistance in water at a known temperature and comparing to the specified values of 244,000 ohms at 20 degrees C and 24,400 ohms at 90 degrees C.
- 02
Loose or corroded thermistor connector
Wiring / connectionThe connector between the discharge pipe thermistor and the PCB may have a poor or intermittent contact due to corrosion, moisture intrusion, or a bent terminal pin. Visually inspect and reseat the connector to check for this condition.
- 03
Damaged wiring harness
Part replacementThe wiring between the thermistor and the PCB may be broken, pinched, or chafed, causing an open or short circuit in the signal line. Check continuity along the full length of the harness with a multimeter.
- 04
Faulty PCB
Part replacementIf the thermistor resistance tests correctly at both reference temperatures and all wiring and connectors are in good condition, the PCB may be misreading the thermistor signal due to an internal fault. PCB replacement is the appropriate next step in this scenario.
Frequently asked questions about 41
What does 41 mean on a LG hvac?
Can I fix error code 41 on my LG HVAC myself?
Is it safe to run my LG HVAC with error code 41 active?
How much does it cost to repair LG HVAC error code 41?
Will resetting my LG HVAC clear error code 41?