Samsung Air Conditioner Error Code E173
Change of EVAP OUT temperature of other indoor unit during piping check.
Change of EVAP OUT temperature of other indoor unit during piping check.
First step from the service manual
Check indoor unit address matches MCU; check EEV connection; verify piping connections.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for E173.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What E173 means on a Samsung air conditioner
Error code E173 on a Samsung air conditioner indicates that the evaporator outlet (EVAP OUT) temperature sensor on a separate indoor unit detected an unexpected temperature change during the piping check sequence. The piping check is an automated commissioning procedure used in multi-split systems to verify that refrigerant is flowing correctly through each indoor unit's piping circuit. During this process, each unit is cycled and monitored for temperature response. If the system detects a temperature shift at the EVAP OUT sensor of a different indoor unit than the one currently being tested, it flags E173 because that cross-response suggests a refrigerant routing problem or an addressing conflict between units.
The most common root causes fall into three categories: indoor unit address mismatches, Electronic Expansion Valve (EEV) faults, and physical piping errors. In a multi-split installation, each indoor unit must have a unique address that matches its MCU (Main Control Unit) configuration. If two units share an address or an address is incorrectly assigned, the system cannot correctly attribute temperature readings to the right unit, triggering this error. An EEV that is stuck open or not responding to control signals can allow refrigerant to flow into the wrong circuit during the piping check, causing an unintended temperature change at the wrong unit's sensor.
Physical piping connection errors, such as liquid and suction lines swapped between indoor units, can also produce this fault. During the piping check, the system expects a defined temperature response from a specific unit. If refrigerant is routed incorrectly due to crossed connections, the EVAP OUT sensor on an adjacent unit registers the change instead. Technicians should confirm address DIP switch or software settings, inspect EEV wiring harnesses and coil resistance, and trace refrigerant piping back to the outdoor unit to rule out crossed connections before clearing and rerunning the piping check.
Source: manufacturer service documentation.
Common causes of E173
- 01
Indoor unit address mismatch
Wiring / connectionIf two or more indoor units share the same address or have incorrect address assignments, the system cannot correctly track which unit is responding during the piping check. Verify DIP switch settings or software address assignments on each indoor unit's control board and confirm they match the MCU configuration.
- 02
Crossed or incorrectly routed refrigerant piping
Wiring / connectionLiquid and suction lines swapped between indoor units cause refrigerant to flow into the wrong circuit during the piping check, registering a temperature change at the wrong EVAP OUT sensor. Physically trace each piping run from the outdoor unit to confirm correct routing and connection points.
- 03
Faulty or disconnected EEV (Electronic Expansion Valve)
Part replacementAn EEV that is stuck in an open position or has a loose wiring harness connection can allow refrigerant flow into an unintended indoor unit during the piping check. Check EEV connector seating, inspect the wiring harness for damage, and verify coil resistance is within specification.
- 04
EVAP OUT temperature sensor fault
Part replacementA defective or poorly connected evaporator outlet temperature sensor on one of the indoor units may report erroneous temperature readings, falsely triggering E173. Inspect the sensor connector and check sensor resistance against the temperature-resistance chart for the unit.
- 05
Wiring or communication error between indoor units and MCU
Wiring / connectionLoose or crossed communication wiring between indoor units and the MCU can cause the system to misidentify which unit is responding to the piping check. Inspect all inter-unit communication wiring for correct polarity, secure termination, and absence of shorts.
Frequently asked questions about E173
What does E173 mean on a Samsung air conditioner?
Can I fix E173 on my Samsung multi-split system myself?
Will resetting the system clear the E173 error code?
Is it safe to run my air conditioner with an E173 error showing?
How much does it cost to repair a Samsung air conditioner showing E173?
78,000+ service manuals · 160,000+ error codes · 55+ brands
Get Started$29/month · Cancel anytime · Or $9.95 3-day pass