Samsung Air Conditioner Error Code E316
Low pressure sensor error OPEN/SHORT
Low pressure sensor error OPEN/SHORT - detected when compressor is ready to operate; SHORT below 0.4V, OPEN over 4.7V.
First step from the service manual
Check sensor wiring; skip detection during oil recovery/safety start/defrost operations.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for E316.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What E316 means on a Samsung air conditioner
The E316 error code on a Samsung air conditioner indicates a low pressure sensor fault, specifically an OPEN or SHORT circuit condition detected in the low pressure sensor circuit. The system monitors the sensor signal voltage and triggers E316 when that voltage falls below 0.4V (SHORT condition) or rises above 4.7V (OPEN condition). This check is performed when the compressor is preparing to operate, making it a pre-start safety gate that prevents the system from running under potentially damaging refrigerant pressure conditions.
The low pressure sensor is a critical component in the refrigerant circuit. It monitors suction-side pressure to protect the compressor from operating with insufficient refrigerant or under vacuum conditions. The sensor outputs an analog voltage signal that the control board reads continuously. When the signal falls outside the acceptable range (approximately 0.4V to 4.7V), the board interprets the reading as a failed or disconnected sensor rather than a valid pressure reading, and E316 is logged.
Importantly, the control logic is designed to skip low pressure detection during oil recovery cycles, safety start sequences, and defrost operations. This means E316 should not trigger during those specific operational modes under normal circumstances. If the error appears at other times, the diagnostic priority is the sensor wiring and connections first, followed by the sensor itself, and then the control board if no wiring faults are found.
Source: manufacturer service documentation.
Common causes of E316
- 01
Loose or disconnected sensor wiring
Wiring / connectionA disconnected or poorly seated connector at the low pressure sensor will cause the signal voltage to read above 4.7V, triggering the OPEN condition. Inspect the wiring harness and connector at the sensor for proper seating and signs of corrosion or pin pullout.
- 02
Damaged or shorted sensor wiring
Wiring / connectionChafed, pinched, or rodent-damaged wiring can cause two conductors to short together, pulling the signal voltage below 0.4V and triggering the SHORT condition. Trace the sensor wiring along the harness route looking for visible damage or contact with sharp edges.
- 03
Failed low pressure sensor
Part replacementThe sensor itself can fail internally, producing a signal voltage outside the valid range even when wiring is intact. If wiring checks out and resistance or voltage readings at the sensor are outside specification, the sensor will need replacement.
- 04
Faulty control board
Part replacementIf the sensor and all wiring test correctly but the error persists, the issue may be in the signal input circuit on the main control board. This is the least common cause and should only be considered after ruling out all sensor and wiring faults.
Frequently asked questions about E316
What does E316 mean on a Samsung air conditioner?
Can I fix E316 on my Samsung air conditioner myself?
Is it safe to keep running my Samsung air conditioner with an E316 error?
Will resetting my Samsung air conditioner clear the E316 error?
How much does it cost to repair an E316 error on a Samsung air conditioner?
78,000+ service manuals · 160,000+ error codes · 55+ brands
Get Started$29/month · Cancel anytime · Or $9.95 3-day pass