Samsung Air Conditioner Error Code OUTDOOR_YELLOW_GREEN_FLICKER_RED_ON
DC fan error (SH12BWHX only)
DC fan error (SH12BWHX only)
First step from the service manual
Check fan motor connection to CN01 on outdoor control board
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for OUTDOOR_YELLOW_GREEN_FLICKER_RED_ON.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What OUTDOOR_YELLOW_GREEN_FLICKER_RED_ON means on a Samsung air conditioner
The OUTDOOR_YELLOW_GREEN_FLICKER_RED_ON error code on the Samsung SH12BWHX outdoor unit indicates a DC fan motor fault. This code is specific to that model and is communicated through a combination of LED indicator behavior on the outdoor control board: the yellow-green LED flickers while the red LED remains solid. The DC fan motor in the outdoor unit is responsible for drawing air across the condenser coil to reject heat from the refrigerant. When the control board detects an abnormal signal from the fan motor, such as a missing feedback pulse or out-of-range RPM, it flags this fault condition.
The first diagnostic step is to inspect the fan motor's wiring harness connection at connector CN01 on the outdoor control board. A loose, corroded, or damaged connector at this point can interrupt the PWM control signal or the Hall sensor feedback signal, causing the board to register a DC fan error even if the motor itself is functional. DC fan motors on outdoor units rely on continuous rotor position feedback from built-in Hall effect sensors, and any interruption in that signal chain will trigger this fault.
If the CN01 connection is secure and undamaged, the fault likely lies with the DC fan motor itself or with the outdoor control board. DC fan motor failures often result from winding insulation breakdown, bearing seizure, or internal Hall sensor failure. The control board can also develop driver circuit faults that prevent proper motor commutation. Resistance checks on the motor windings and verification of supply voltage at CN01 are the appropriate next steps after confirming connector integrity.
Source: manufacturer service documentation.
Common causes of OUTDOOR_YELLOW_GREEN_FLICKER_RED_ON
- 01
Loose or disconnected CN01 connector
Wiring / connectionThe fan motor wiring harness connection at CN01 on the outdoor control board may be partially seated, corroded, or vibrated loose. This is the first point to inspect and is a common cause of intermittent or persistent DC fan faults.
- 02
DC fan motor failure
Part replacementThe outdoor DC fan motor may have failed due to bearing seizure, winding damage, or internal Hall effect sensor failure. A seized or electrically failed motor will prevent the control board from receiving the rotor feedback signal it expects.
- 03
Damaged fan motor wiring harness
Part replacementThe wiring between CN01 and the fan motor can be chafed, pinched, or broken, especially if routed near moving parts or sheet metal edges. Inspect the full harness length for visible damage or shorts to ground.
- 04
Outdoor control board fault
Part replacementIf the fan motor and all wiring check out correctly, the outdoor control board's DC fan driver circuit may have failed. This prevents proper PWM output to the motor and can produce this error code.
- 05
Fan blade obstruction or mechanical binding
Wiring / connectionDebris lodged in the fan blade or a deformed blade contacting the fan shroud can cause the motor to stall under load, resulting in the control board detecting a rotor speed fault.
Frequently asked questions about OUTDOOR_YELLOW_GREEN_FLICKER_RED_ON
What does OUTDOOR_YELLOW_GREEN_FLICKER_RED_ON mean on a Samsung air_conditioner?
Can I fix the DC fan error on my Samsung outdoor unit myself?
Is it safe to keep running my Samsung air conditioner with this error active?
Will resetting my Samsung air conditioner clear this error code?
How much does it cost to repair a DC fan error on a Samsung outdoor unit?
78,000+ service manuals · 160,000+ error codes · 55+ brands