mypros+
Error code reference

Samsung Air Conditioner Error Code P407

High pressure sensor protection

High pressure sensor protection – compressor stops when condensate pressure exceeds 28 kg/cm²G.

First step from the service manual

Check for overcharged refrigerant; check indoor/outdoor fan motor operation.

The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.

MyPros+ Max

Get the full diagnostic procedure for P407.

  • Step-by-step tests with expected resistance, voltage, and continuity values
  • Wiring diagram references and connector pinouts from the OEM service manual
  • Verified part numbers when replacement is required
Get the full procedure

$29/month · Cancel anytime · Or $9.95 3-day pass

What P407 means on a Samsung air conditioner

Error code P407 on a Samsung air conditioner indicates high pressure sensor protection has been triggered. This fault occurs when the condensate (discharge) pressure in the refrigerant circuit exceeds 28 kg/cm²G, at which point the system automatically shuts down the compressor to prevent mechanical damage. The high pressure sensor continuously monitors discharge-side pressure and signals the control board to interrupt compressor operation when this threshold is crossed. This is a protective function, not a random fault, meaning an underlying condition is forcing refrigerant pressure beyond safe operating limits.

The most common causes fall into two categories: refrigerant-side issues and airflow-related issues. On the refrigerant side, an overcharged system contains more refrigerant than the circuit is designed to handle, which drives discharge pressure up rapidly, especially during periods of high ambient temperature. On the airflow side, if either the indoor evaporator fan or the outdoor condenser fan is not operating correctly, heat exchange is compromised. A failed or underperforming outdoor fan allows heat to build up in the condenser coil, raising head pressure significantly. A restricted indoor fan reduces the heat load being pulled from the space but can also contribute to system imbalance.

Diagnosing P407 requires confirming whether the refrigerant charge is within specification using manifold gauges, and physically verifying that both indoor and outdoor fan motors are spinning at the correct speed. Blocked condenser coils, dirty filters, or failed fan capacitors can all produce the same elevated pressure symptom. Addressing the root cause is essential before restarting the system, as repeated high pressure events can damage compressor valves and reduce unit lifespan.

Source: manufacturer service documentation.

Common causes of P407

  1. 01

    Overcharged refrigerant

    Wiring / connection

    Too much refrigerant in the system drives discharge pressure above the 28 kg/cm²G cutoff threshold. This is identified by connecting manifold gauges and comparing actual charge pressure to the unit's specified operating range.

  2. 02

    Outdoor condenser fan failure

    Part replacement

    If the outdoor fan motor is not running or is running below rated speed, heat cannot be properly rejected from the condenser coil, causing head pressure to spike. Check that the fan blade spins freely and the motor runs when the unit calls for cooling.

  3. 03

    Indoor evaporator fan failure

    Part replacement

    A non-functioning or slow indoor fan reduces airflow across the evaporator, disrupting the refrigerant cycle balance and contributing to elevated system pressure. Verify the indoor blower is operating at normal speed during a cooling cycle.

  4. 04

    Blocked or dirty condenser coil

    Wiring / connection

    Accumulated dirt, debris, or vegetation on the outdoor condenser coil restricts airflow and traps heat, raising discharge pressure even if the fan motor is functional. Inspect the coil fins and clean them if airflow is visibly restricted.

  5. 05

    Faulty high pressure sensor

    Part replacement

    In less common cases, the pressure sensor itself may be reading incorrectly and triggering protection at normal operating pressures. This should only be suspected after refrigerant charge and fan operation have been confirmed as normal.

See the test procedure for each cause

Frequently asked questions about P407

What does P407 mean on a Samsung air conditioner?
P407 is a high pressure sensor protection fault. It means the refrigerant discharge pressure exceeded 28 kg/cm²G, causing the system to shut down the compressor automatically. The code is a safety response designed to prevent compressor damage, and it points to an underlying condition such as overcharged refrigerant or inadequate airflow through the indoor or outdoor coils.
Can I fix a P407 error myself?
Some contributing factors, like a dirty outdoor condenser coil or a clogged indoor air filter, can be addressed by a homeowner. However, checking and correcting refrigerant charge requires EPA-certified equipment and training that most homeowners do not have. Fan motor diagnosis also benefits from electrical testing tools. It is safest to have a certified HVAC technician perform the full diagnostic before restarting the unit.
Is it safe to keep running my air conditioner with a P407 error?
No. The P407 code means the system has already shut the compressor down as a protective measure. Attempting to bypass or repeatedly reset the unit without correcting the root cause can lead to compressor valve damage or complete compressor failure. The system should remain off until a technician identifies and resolves the cause of the elevated pressure.
Will resetting the unit clear the P407 error?
A power reset may clear the error temporarily and allow the compressor to restart, but if the underlying cause is not corrected, the pressure will exceed the 28 kg/cm²G limit again and P407 will return. Repeated resets without a repair can accelerate wear on the compressor. The fault should be diagnosed and resolved before relying on a reset as a solution.
How much does it cost to repair a Samsung air conditioner showing P407?
Repair costs vary depending on the root cause. A refrigerant adjustment or coil cleaning typically runs in the range of $75 to $200 for labor and materials. If a fan motor needs replacement, expect costs in the range of $150 to $400 depending on the motor and labor rates in your area. Compressor damage resulting from unaddressed high pressure events can push repair costs significantly higher, sometimes exceeding $800 to $1,500 or more.

78,000+ service manuals · 160,000+ error codes · 55+ brands

Get Started

$29/month · Cancel anytime · Or $9.95 3-day pass