mypros+
Error code reference

LG Hvac Error Code 43

High pressure switch opened, over 600 PSI.

High pressure switch opened, over 600 PSI.

MyPros+ Max

Get the full diagnostic procedure for 43.

  • Step-by-step tests with expected resistance, voltage, and continuity values
  • Wiring diagram references and connector pinouts from the OEM service manual
  • Verified part numbers when replacement is required
Get the full procedure

$29/month · Cancel anytime · Or $9.95 3-day pass

What 43 means on a LG hvac

Error code 43 on an LG HVAC system indicates that the high pressure switch has opened due to refrigerant pressure exceeding 600 PSI on the high side of the refrigerant circuit. The high pressure switch is a safety device wired into the compressor control circuit. When pressure climbs past the switch's rated cutout point, it opens the circuit and shuts down the compressor to prevent mechanical damage. This is a protective response, not a component failure in itself, meaning the underlying condition that drove pressure above 600 PSI must be identified and corrected.

The most frequent causes of excessive high-side pressure involve restricted heat rejection. If the outdoor condenser coil is blocked by dirt, debris, or vegetation, heat cannot transfer out of the refrigerant efficiently, causing pressure to climb. Similarly, a failed or slow condenser fan motor reduces airflow across the coil and produces the same result. Refrigerant overcharge is another significant contributor: too much refrigerant in the system raises both suction and discharge pressures, and even a moderate overcharge can push high-side pressure into fault territory under warm ambient conditions.

Non-condensable gases such as air or nitrogen trapped in the refrigerant circuit also elevate high-side pressure disproportionately. A restricted liquid line or a failing expansion valve that does not meter refrigerant correctly can also contribute. Once the root cause is addressed, the switch may reset automatically as pressure drops, or it may require a manual reset depending on the specific switch type installed in the unit. Technicians should always measure actual high-side pressure with a manifold gauge set before assuming the switch itself is faulty.

Source: manufacturer service documentation.

Common causes of 43

  1. 01

    Blocked or dirty condenser coil

    Wiring / connection

    Dirt, debris, or vegetation clogging the outdoor condenser coil prevents heat from escaping the refrigerant, causing high-side pressure to spike. Inspect the coil visually and clean it with a coil cleaner and water rinse if airflow is obstructed.

  2. 02

    Condenser fan motor failure

    Part replacement

    A condenser fan motor that has seized, slowed, or stopped running reduces airflow over the coil dramatically, which drives refrigerant pressure above safe limits. Check that the fan spins freely and verify the motor draws correct amperage.

  3. 03

    Refrigerant overcharge

    Wiring / connection

    Too much refrigerant in the system raises high-side pressure above normal operating ranges, especially during warmer ambient temperatures. Diagnosis requires connecting a manifold gauge set and comparing actual pressures to the system's charging chart.

  4. 04

    Non-condensable gases in the refrigerant circuit

    Wiring / connection

    Air or nitrogen introduced during servicing remains in the high side and causes abnormally elevated discharge pressure that does not correspond to the refrigerant's normal pressure-temperature relationship. A manifold gauge reading compared against refrigerant saturation tables will reveal the discrepancy.

  5. 05

    Faulty high pressure switch

    Part replacement

    In less common cases, the high pressure switch itself may be opening prematurely due to calibration drift or internal failure, even when actual system pressure is within normal range. Confirm actual pressure with gauges before condemning the switch.

See the test procedure for each cause

Frequently asked questions about 43

What does 43 mean on a LG hvac?
Error code 43 on an LG HVAC system means the high pressure switch has opened because refrigerant pressure on the high side of the system exceeded 600 PSI. This is a safety shutdown designed to protect the compressor from damage. The system will not restart normally until the pressure drops and the underlying cause is corrected.
Can I fix error code 43 myself, or do I need a technician?
Some causes are accessible to a knowledgeable homeowner, such as clearing debris from around the outdoor unit or cleaning a visibly blocked condenser coil. However, diagnosing refrigerant overcharge, non-condensable gases, or a failed fan motor requires manifold gauges and electrical testing equipment. Working with refrigerant also requires EPA Section 608 certification in the United States, so a licensed HVAC technician is needed for those repairs.
Is it safe to keep running my HVAC system when error code 43 appears?
No, you should not attempt to override or bypass the high pressure switch and continue operating the system. Pressures above 600 PSI can cause compressor failure, refrigerant line rupture, or fitting failures, all of which create safety hazards and very costly damage. Leave the system off until a technician has diagnosed and corrected the cause of the high pressure condition.
Will resetting the unit clear error code 43?
Resetting the unit by cycling power may temporarily clear the fault if the high pressure switch resets automatically once pressure drops. However, the error code will return as soon as the system runs and pressure rises again, because the root cause has not been addressed. A reset is useful for confirming the fault is repeatable, but it is not a repair.
How much does it cost to repair an LG HVAC unit showing error code 43?
Repair costs vary widely depending on the cause. A condenser coil cleaning or fan blade replacement may cost between $100 and $300 in labor and parts. A failed condenser fan motor replacement typically runs $200 to $500. If refrigerant recovery, evacuation, and recharge are needed to correct an overcharge or remove non-condensables, expect costs in the $300 to $700 range. Compressor damage resulting from delayed repair can push costs significantly higher.

78,000+ service manuals · 160,000+ error codes · 55+ brands

Get Started

$29/month · Cancel anytime · Or $9.95 3-day pass