mypros+
Error code reference

GE Range Error Code SUPPLY OPEN NEUTRAL

Power monitor detects open neutral

Power monitor detects open neutral — L1-N voltage below 90VAC.

First step from the service manual

Check neutral wiring connection at terminal block and branch circuit.

The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.

MyPros+ Max

Get the full diagnostic procedure for SUPPLY OPEN NEUTRAL.

  • Step-by-step tests with expected resistance, voltage, and continuity values
  • Wiring diagram references and connector pinouts from the OEM service manual
  • Verified part numbers when replacement is required
Get the full procedure

$29/month · Cancel anytime · Or $9.95 3-day pass

What SUPPLY OPEN NEUTRAL means on a GE range

The SUPPLY OPEN NEUTRAL error on a GE range is triggered by the appliance's internal power monitor when it detects that the L1-to-neutral voltage has dropped below 90VAC. In a properly functioning 240VAC residential circuit, the neutral conductor balances the two hot legs (L1 and L2), and each leg should measure approximately 120VAC to neutral. When the neutral connection is lost or severely degraded, this voltage balance collapses, causing one or both legs to read abnormally high or low relative to neutral. The range detects this condition and displays the error to prevent damage to sensitive electronics and heating components.

The most common source of an open neutral is a failed or loose connection at the range's terminal block, where the incoming supply wires attach to the appliance. Over time, these connections can loosen due to thermal cycling, corrosion, or improper torque during installation. An open neutral can also originate further upstream at the wall receptacle, the branch circuit wiring, or even at the main electrical panel where the neutral bus connection may have failed. A broken neutral wire within the conduit or cable run is less common but possible, particularly in older homes with aluminum wiring.

This condition is a genuine electrical supply problem, not a range component failure. The appliance itself is reporting what it measures at the input terminals. Diagnostics should begin at the terminal block on the range, then work upstream toward the panel. A multimeter is required to confirm voltages at each point. Because open neutral conditions can produce overvoltage on one leg, the range should not be operated until the fault is corrected.

Source: manufacturer service documentation.

Common causes of SUPPLY OPEN NEUTRAL

  1. 01

    Loose or failed neutral connection at the range terminal block

    Wiring / connection

    The neutral wire at the terminal block on the back of the range may have loosened or corroded over time. Inspect the terminal block for a loose screw, discoloration, or burnt insulation at the neutral terminal.

  2. 02

    Faulty or burnt range power cord

    Part replacement

    If the range uses a removable power cord, the neutral conductor within the cord may be broken internally or the neutral prong connection may have failed. Inspect the cord and its plug for heat damage, melting, or physical breaks.

  3. 03

    Loose neutral connection at the wall receptacle or junction box

    Wiring / connection

    The neutral wire at the 240VAC wall receptacle may have pulled loose from its terminal. Turn off the breaker and inspect the receptacle wiring for loose or corroded connections.

  4. 04

    Open neutral at the electrical panel

    Wiring / connection

    The neutral wire from the branch circuit may have a loose or failed connection at the neutral bus bar in the main panel. This requires a licensed electrician to inspect safely, as the panel involves live conductors.

  5. 05

    Broken neutral conductor in branch circuit wiring

    Wiring / connection

    The neutral wire running through the wall between the panel and the receptacle may be damaged or broken, particularly in older homes with aluminum wiring or in cases of physical damage to the cable. This is less common but requires a full circuit inspection.

See the test procedure for each cause

Frequently asked questions about SUPPLY OPEN NEUTRAL

What does SUPPLY OPEN NEUTRAL mean on a GE range?
SUPPLY OPEN NEUTRAL means the range's internal power monitor has detected that the voltage between the L1 hot leg and the neutral conductor has dropped below 90VAC. This indicates the neutral wire in your electrical supply is open, broken, or has a failed connection somewhere between the range and your electrical panel. It is a supply-side electrical fault, not an internal range component failure.
Is it safe to use my GE range when SUPPLY OPEN NEUTRAL is displayed?
No, you should not operate the range while this error is active. An open neutral condition can cause one leg of the 240VAC supply to carry overvoltage, which can damage the range's electronics and heating components. The condition also represents a wiring fault that poses a potential fire or shock hazard and should be corrected before resuming use.
Will resetting the range clear the SUPPLY OPEN NEUTRAL error?
Resetting the range by cycling the breaker will not permanently clear this error if the underlying wiring fault remains. The power monitor will detect the low neutral voltage again when the range is powered back on and the error will return. The fault must be corrected at the source before the error will stay cleared.
How do I fix the SUPPLY OPEN NEUTRAL error on a GE range?
Start by turning off the breaker and inspecting the neutral wire connection at the terminal block on the back of the range, looking for looseness, corrosion, or burn marks. If that connection is secure, check the wall receptacle or power cord connections next. If the fault is not found at the range or receptacle, the issue is likely at the panel or in the branch circuit wiring and will require a licensed electrician to diagnose and repair.
How much does it cost to repair the SUPPLY OPEN NEUTRAL error on a GE range?
The cost depends on where the fault is located. If the fix is simply retightening a loose wire at the terminal block or replacing a power cord, the cost is relatively low, typically in the range of $20 to $150 including parts and labor. If the problem is at the wall receptacle or within the branch circuit wiring, electrician labor costs will apply, generally ranging from $100 to $400 or more depending on the complexity of the repair and local rates.

78,000+ service manuals · 160,000+ error codes · 55+ brands

Get Started

$29/month · Cancel anytime · Or $9.95 3-day pass