Samsung Air Conditioner Error Code E403
Prohibit starting by low pressure
Prohibit starting by low pressure - low pressure sensor value below 3.1 kg/cm2G during cooling or below 2.6 kg/cm2G during heating for 3 consecutive seconds before pump down start.
First step from the service manual
Measure pressure using manifold gauge when system is stopped.
The complete diagnostic procedure includes additional test steps, resistance specifications, wiring diagram references, and component test points.
Get the full diagnostic procedure for E403.
- Step-by-step tests with expected resistance, voltage, and continuity values
- Wiring diagram references and connector pinouts from the OEM service manual
- Verified part numbers when replacement is required
$29/month · Cancel anytime · Or $9.95 3-day pass
What E403 means on a Samsung air conditioner
Error code E403 on a Samsung air conditioner is a low pressure lockout fault. The system monitors suction-side refrigerant pressure through a low pressure sensor, and E403 triggers when that sensor reads below 3.1 kg/cm2G during a cooling operation or below 2.6 kg/cm2G during a heating operation for 3 consecutive seconds before pump down begins. The control board interprets these readings as an unsafe operating condition and prohibits the compressor from starting to prevent damage from running on insufficient refrigerant charge or a restricted system.
The most frequent root cause of E403 is low refrigerant charge, typically the result of a leak in the refrigerant circuit at service valves, flare connections, or coil joints. A refrigerant shortage drops suction pressure below the threshold values the system requires before allowing startup. Other causes include a blocked or restricted filter drier or expansion valve that reduces pressure on the low side, or a faulty low pressure sensor that is sending an inaccurate signal to the control board even when actual system pressure is adequate. A malfunctioning sensor can produce false E403 faults without any actual refrigerant loss.
The correct first diagnostic step is to connect a manifold gauge set to the system service ports while the unit is stopped and measure static pressure. If static pressure is normal for the refrigerant type and ambient temperature, the sensor or its wiring circuit should be suspected. If pressure is genuinely low, the system should be leak-checked before any refrigerant is added, as topping off a leaking system is only a temporary measure and refrigerant handling requires proper certification.
Source: manufacturer service documentation.
Common causes of E403
- 01
Low refrigerant charge due to a leak
Wiring / connectionA leak at flare connections, service valves, or coil joints allows refrigerant to escape, dropping suction pressure below the 3.1 kg/cm2G (cooling) or 2.6 kg/cm2G (heating) threshold. Connect a manifold gauge to confirm low static pressure, then perform a leak search before recharging.
- 02
Faulty low pressure sensor
Part replacementA defective low pressure sensor can report falsely low pressure values to the control board even when actual system pressure is within normal range. If manifold gauge readings are normal but E403 persists, the sensor and its wiring should be tested and replaced if defective.
- 03
Restricted or blocked expansion valve
Part replacementA clogged or stuck-closed expansion valve reduces refrigerant flow and can cause suction pressure to drop sharply on the low side. This restriction will produce abnormally low suction pressure readings on the manifold gauge despite adequate refrigerant charge.
- 04
Blocked or saturated filter drier
Part replacementA restricted filter drier creates a pressure drop in the liquid line that can propagate to the low side of the system, reducing suction pressure below the sensor threshold. A significant temperature differential across the drier is a common indicator of this condition.
- 05
Wiring fault in the sensor circuit
Wiring / connectionDamaged, corroded, or loose wiring between the low pressure sensor and the control board can cause erroneous low-pressure signals. Inspect the sensor connector and wiring harness for corrosion, breaks, or loose terminals before condemning the sensor or refrigerant circuit.
Frequently asked questions about E403
What does E403 mean on a Samsung air conditioner?
Can I fix E403 on my Samsung air conditioner myself?
Is it safe to keep running my air conditioner with an E403 error?
How much does it cost to repair an E403 error on a Samsung air conditioner?
Will resetting my Samsung air conditioner clear the E403 error?